Skip to main content
True Trade Path

Diagnostic · Free

Superheat & Subcooling Calculator

Convert pressure and temperature readings into superheat and subcooling to diagnose charge.

System

Saturation data runs 11–461 psig for this refrigerant.

Metering device
Suction side

Read pressure at the service valve and line temperature with a clamp probe about six inches upstream, insulated from ambient air.

psig
°F
Liquid side
psig
°F
Conditions

These set the charted target superheat on a fixed-orifice system. On a TXV or EEV the valve sets superheat itself, so they are context only.

°F

Return air wet bulb at the indoor coil.

°F

Ambient at the condenser, out of direct sun.

Subcooling

10.3°Fmeasured

A TXV or EEV holds superheat itself, so subcooling is the charge indicator. Target is 8–12°F.
SuperheatTarget 8–14°F
10.1°F
Evaporator saturationInterpolated at 125 psig
44.9°F
Condensing saturationInterpolated at 380 psig
115.3°F
Condenser splitCondensing temp above ambient; 20–30°F is typical
20.3°F

Charge appears correct

10.1°F superheat and 10.3°F subcooling both land inside the expected window. If the system still is not cooling, the fault is somewhere other than the charge — check airflow, blower speed, duct leakage into unconditioned space, and the compressor's own capacity.

Verify airflow before you touch the charge

Low airflow produces readings that look exactly like an undercharge. Adding refrigerant to a system with a loaded filter, a dirty blower wheel or a collapsed flex duct floods the compressor with liquid and destroys it. Measure total external static pressure against the blower table and check the temperature split first — every single time, before this page means anything.

EPA Section 608 certification is legally required

Only a Section 608 certified technician may purchase, handle or recover refrigerant. Venting refrigerant to the atmosphere is a federal violation under the Clean Air Act, and the penalties fall on the individual as well as the company.
Reading the combinations
SuperheatSubcoolingWhat it points toWhere to look
In rangeIn rangeCharge is correctMove on to airflow, blower speed and duct static
HighLowUnderchargeWeigh in refrigerant after finding and repairing the leak
LowHighOverchargeRecover to the target; check for a previous top-off
HighHighLiquid line restrictionFilter drier, kinked liquid line, partially closed valve
LowLowMetering device overfeedingSensing bulb contact and insulation, valve superheat setting, wrong piston
HighIn rangeRestricted or undersized metering deviceCompare the piston size against the nameplate
In rangeLowNon-condensables or a flooded condenserCondenser coil, fan speed, and whether the system was evacuated properly

Saturation temperatures are interpolated linearly between published pressure-temperature points spaced five to ten degrees apart, which holds accuracy well inside the tolerance of a field gauge set. R-410A, R-454B and R-32 values are dew point, which is what a suction gauge reads; R-454B carries roughly 2°F of glide, so a bubble-point subcooling reading on that refrigerant runs slightly cooler than shown here. Always charge to the equipment manufacturer's own chart when one is on the unit.

What this assumes

  • Saturation temperatures are interpolated from published pressure-temperature data for the selected refrigerant.
  • Fixed-orifice systems are evaluated on superheat; TXV and EEV systems are evaluated on subcooling.
  • Assumes airflow has been verified first — charge cannot be judged on a system with restricted airflow.

Important

Only EPA Section 608 certified technicians may purchase, handle or recover refrigerant. Venting refrigerant to the atmosphere is a federal violation under the Clean Air Act.

Understanding the result

Verify airflow before you touch the charge

Low airflow produces readings that look exactly like undercharge. Adding refrigerant to a system with a dirty filter or a collapsed flex duct floods the compressor and destroys it. Check static pressure and temperature split first, every time.

Which number to trust

On a fixed-orifice system, superheat reflects charge and you charge to a target superheat from a chart based on indoor wet bulb and outdoor dry bulb. On a TXV or EEV system the valve holds superheat constant, so subcooling is the meaningful indicator — typically 8 to 12°F.

Reading the combinations

High superheat with low subcooling points to undercharge. Low superheat with high subcooling points to overcharge. High superheat with high subcooling suggests a liquid line restriction. Low superheat with low subcooling usually means the metering device is overfeeding.