Calculator · Free
Voltage Drop Calculator
Check whether a conductor run stays inside the 3% branch-circuit voltage drop recommendation.
Voltage drop
2.59%6.2 V
- Voltage at the loadFrom 240 V at the source
- 233.8 V
- Drop in voltsCopper 8 AWG at 0.7780 Ω/1000 ft
- 6.22 V
- Maximum run at 3%One-way, at this size and load
- 116 ft
- Power lost in the conductorHeat, paid for and not used
- 249 W
Within the 3% recommendation
| Size | Ω per 1000 ft | Drop | Drop % | Max run at limit |
|---|---|---|---|---|
| 8 AWG — selected | 0.7780 | 6.22 V | 2.59% | 116 ft |
| 6 AWG | 0.4910 | 3.93 V | 1.64% | 183 ft |
| 4 AWG | 0.3080 | 2.46 V | 1.03% | 292 ft |
| 3 AWG | 0.2450 | 1.96 V | 0.82% | 367 ft |
| 2 AWG | 0.1940 | 1.55 V | 0.65% | 464 ft |
| 1 AWG | 0.1540 | 1.23 V | 0.51% | 584 ft |
What this assumes
- Uses NEC Chapter 9, Table 8 DC resistance for uncoated copper and aluminum at 75°C.
- Single-phase drop uses 2 × length; three-phase uses 1.732 × length.
- Alternating current effects such as reactance are not modeled; for large conductors in steel raceway, actual drop can be higher.
Important
NEC 210.19(A) Informational Note recommends a maximum 3% drop on a branch circuit and 5% on the combined feeder and branch circuit. These are recommendations, not enforceable requirements, except where a specific article states otherwise.
Understanding the result
Why voltage drop matters
Every conductor has resistance, so voltage at the load is always lower than voltage at the source. Excessive drop makes motors run hot and draw more current, dims lighting, and causes electronics to reset. The longer the run and the higher the current, the more conductor you need to hold the drop down.
The 3% and 5% figures
The NEC recommends holding a branch circuit to 3% and the feeder plus branch circuit combined to 5%. Because these appear in an Informational Note, they are not enforceable in most installations — but designers, specifications and many local amendments treat them as mandatory.
What to do when the drop is too high
Increase the conductor size, shorten the run, raise the supply voltage where the equipment allows it, or split the load across multiple circuits. Upsizing conductors for voltage drop is the usual answer, and the equipment grounding conductor must be upsized proportionally under NEC 250.122(B).
Common questions
Is 3% voltage drop a code requirement?
Do I need to upsize the ground wire too?
You may also need
The next decision usually follows directly from this one.
- CalculatorWire Size CalculatorFind the minimum conductor size for a load based on ampacity, temperature, bundling and distance.
- CalculatorOhm's Law CalculatorSolve for volts, amps, ohms or watts from any two known values.
- CalculatorDwelling Load CalculatorRun a standard NEC Article 220 dwelling load calculation to size a residential service.
- CalculatorConduit Fill CalculatorCheck conductor fill against NEC Chapter 9 limits and find the trade size you need.