Pipe Volume & Fill Calculator

Calculate the water volume, weight and fill time of a pipe run for flushing and testing.

Pipe

The standard wall thickness for potable water distribution in most jurisdictions.

Volume is driven by the actual bore, not the trade size.

ft

Total footage of this size and material in the system.

gpm

Fill rate at the supply, or gravity drain rate. Used for the timing figure.

Volume of 150 ft of 3/4" Copper, Type L

3.77 gal0.50 ft³

0.0251 gal per foot at a 0.785 in. bore.
Gallons per foot2.51 gal per 100 ft
0.0251 gal
Weight of the waterAt 8.34 lb per gallon — hanger and support load
31.5 lb
Fill or drain timeAt 8.0 gpm with no downstream restriction
28 sec
Velocity at that flowInside the usual 8 ft/s working limit
5.3 ft/s

Use this figure for chemical dosing, not just curiosity

A 3.77 gallon system volume is what sets your chlorination dose, your glycol charge and the water you have to displace on a pressure test. On a hydronic loop, getting the glycol ratio wrong in either direction either freezes the loop or gels it.
Gallons per 100 ft — Copper, Type L
NominalInside diameterGallons per footGallons per 100 ftWater weight per 100 ft
1/2"0.545 in0.01211.2110.1 lb
3/4" — selected0.785 in0.02512.5121.0 lb
1"1.025 in0.04294.2935.7 lb
1-1/4"1.265 in0.06536.5354.5 lb
1-1/2"1.505 in0.09249.2477.1 lb
2"1.985 in0.160816.08134.1 lb
2-1/2"2.465 in0.247924.79206.8 lb
3"2.945 in0.353935.39295.1 lb
This run, expressed every way you will need it
MeasureBasisValue
Gallonsπ/4 × d² × length ÷ 231 in³ per gal3.77
Cubic feetGallons ÷ 7.4810.504
LitersGallons × 3.78514.3
Water weightGallons × 8.34 lb31.5 lb
Fill or drain timeGallons ÷ 8.0 gpm28 sec

What this assumes

  • Uses nominal pipe inside diameters for common copper, PEX, PVC and steel sizes.
  • Water density is taken at 8.34 lb per gallon at room temperature.
  • Fill time assumes constant supply flow with no restriction downstream.

Understanding the result

Why volume matters on service work

Chlorination, glycol charging and system flushing all require knowing how much liquid a system holds. Guessing means either wasting chemical or under-treating the system, and on a hydronic loop an incorrect glycol ratio can either freeze or gel.